5SU1356-7KK16 Siemens Residual protective devices

 29.80

  • 5SU1356-7KK16
  • RCBO
  • Type A
  • 1 + N pole
  • 230 V
  • C 16 A
  • IF 30 mA
  • 6 kA

Residual protective devices Siemens 5SU1356-7KK16

5SU1356-7KK16

RCBO, 6 kA, 1P+N, type A, 30 mA, C-Char, In: 16 A, Un AC: 230 V

Download

DataSheet in PDF

Weight 0.272 kg
Dimensions 40.00 × 96.00 × 82.00 mm
Brand

SIEMENS

product brand name

SENTRON

product designation

RCBO

design of the product

Instantaneous

number of poles

2

number of poles / with protection

1

tripping characteristic class

C

mechanical service life (switching cycles) / typical

10 000

overvoltage category

III

degree of pollution

2

type of voltage / of the operating voltage

AC

insulation voltage (Ui) / rated value

264 V

surge voltage resistance / rated value

4 000 V

surge current resistance / at (8/20) µs

1 kA

supply voltage

● for testing equipment / minimum

195 V

operating frequency

50 Hz

supply voltage frequency / rated value

50 Hz

protection class IP

IP20, if the distribution board is installed, with connected conductors

breaking capacity short-circuit current (Icn) / according to EN 61009-1 / rated value

6 kA

switching capacity current

● acc. to EN 60898 / rated value

6 kA

● acc. to IEC 60947-2 / rated value

15 kA

rated residual switching capacity (IΔm) / according to IEC 61009-1

6 kA

energy limitation class

3

power loss [W]

● for rated value of the current / at AC / in hot operating state / per pole

2.8 W

tripping fault current / rated value

30 mA

operational current

● at 30 °C / rated value

16 A

● at 40 °C / rated value

15.2 A

● at 45 °C / rated value

14.88 A

● at 50 °C / rated value

14.4 A

● at 55 °C / rated value

13.92 A

● at 60 °C / rated value

13.6 A

● at 65 °C / rated value

12.96 A

● at 70 °C / rated value

12.32 A

● at AC / rated value

16 A

residual current type

A

product component / neutral conductor switching

Yes

product feature / touch protection

Yes

product feature

● halogen-free

Yes

● silicon-free

Yes

connectable conductor cross-section / solid

connectable conductor cross-section / stranded

connectable conductor cross-section / finely stranded / with core end processing

tightening torque / with screw-type terminals

position / of power supply cord

Either top or bottom

installation depth

70 mm

number of modular width units

2

mounting position

any

weight / with packaging

269 g

influence of the surrounding temperature

Max. 95% humidity

ambient temperature / during operation

ambient temperature / during storage

● minimum

-40 °C

● maximum

75 °C

number of test cycles / for environmental testing / acc. to IEC 60068-2-30

28

reference code

● acc. to DIN EN 61346-2

F

● acc. to IEC 81346-2

F