5SV3312-6 Siemens Residual current circuit breaker

 19.20

  • 5SV3312-6
  • RCBO
  • Type A
  • 1 + N pole
  • 230 V
  • Rated current: 25 A
  • Residual current: 30 mA

Residual current circuit breaker Siemens 5SV3312-6

5SV3312-6

Residual current operated circuit breaker, 2-pole, type A, In: 25 A, 30 mA, Un AC: 230 V

Download

DataSheet in PDF

Weight 0.187 kg
Dimensions 97.00 × 42.00 × 85.00 mm
Brand

SIEMENS

product brand name

SENTRON

product designation

RCCB

design of the product

Instantaneous

number of poles

2

size of installation devices / acc. to DIN 43880

1

mechanical service life (switching cycles) / typical

10 000

short-circuit current / of series fuse / maximum permissible

63 A

short-circuit current rating

10 kA

switching function / short-term delayed

No

overvoltage category

III

supply voltage

● for testing equipment / minimum

195 V

operating frequency

50 Hz

supply voltage frequency / rated value

50 Hz

protection class IP

IP20, if the distribution board is installed, with connected conductors

switching capacity current

● acc. to EN 60898 / rated value

0.5 kA

● according to IEC 61008-1 / rated value

0.5 kA

power loss [W]

● for rated value of the current / at AC / in hot operating state / per pole

1 W

tripping fault current / rated value

30 mA

operational current

● at 40 °C / rated value

25 A

● at 45 °C / rated value

25 A

● at 50 °C / rated value

25 A

● at 55 °C / rated value

25 A

● at 60 °C / rated value

25 A

● at 65 °C / rated value

23.3 A

● at 70 °C / rated value

17.6 A

● at AC / rated value

25 A

residual current type

A

let-through current / permissible

5 200 kA

I2t value / permissible

58 000 A²·s

surge current resistance / rated value

1 kA

product feature / silicon-free

Yes

product extension / installable / supplementary devices

Yes

connectable conductor cross-section / solid

connectable conductor cross-section / stranded

tightening torque / with screw-type terminals

position / of power supply cord

top or bottom

installation depth

70 mm

number of modular width units

2

fastening method

DIN rail (REG)

mounting position

any

ambient temperature / during operation

● minimum

-25 °C

● maximum

45 °C

ambient temperature / during storage

● minimum permissible

-40 °C

● maximum permissible

75 °C

number of test cycles / for environmental testing / acc. to IEC 60068-2-30

28

Transport Information