SIEMENS
Siemens 3VA5110-4ED31-0AA0 Circuit Breaker 3VA5 UL Frame 125, 3-Pole, 25 kA @ 480 V Original Brand New
High-performance 3-pole molded case circuit breaker from the 3VA5 UL Frame 125 series. Designed for robust line protection, it features a 100A current rating, TM210 thermal-magnetic trip unit, and a 25kA breaking capacity at 480V.
- ConditionOriginal Brand New
- Warranty12 months
- Genuine Products
- Up to 1-Year Warranty
- Global Shipping
- Secure Payment
- PI / Bank Transfer Available
- Bulk Quote Support
Description
Overview
The Siemens 3VA5110-4ED31-0AA0 is a robust and reliable 3-pole circuit breaker designed for industrial and commercial electrical systems. Part of the 3VA5 UL Frame 125 series, it offers superior breaking capacity and protection to safeguard your electrical installations. Engineered for performance, this circuit breaker ensures optimal line protection with minimal maintenance.
Key Features & Benefit
-
High Breaking Capacity: 25 kA at 480 V ensures maximum safety during overloads or short-circuits.
-
3-Pole Protection: Provides comprehensive protection for three-phase electrical circuits.
-
Line Protection TM210 & FTFM: Advanced line protection mechanisms for enhanced reliability.
-
Overload Protection: In=100 A with permanently set short-circuit protection (Ii=10 x In) ensures long-term stability.
-
Durable & Reliable: Siemens quality guarantees long-lasting performance and minimal downtime.
-
Versatile Application: Ideal for industrial, commercial, and high-demand electrical setups.
Function
-
Circuit Interruption: Automatically cuts off electrical flow during overload or short-circuit conditions.
-
Line Monitoring: TM210 and FTFM functions provide precise line protection.
-
Permanent Short-Circuit Protection: Ensures system safety with preset Ii=10 x In trip rating.
-
Easy Integration: Compatible with standard 3VA5 UL Frame 125 electrical panels.
Visit 3VA5110-4ED31-0AA0 for more detail info
For more our products visit turll
Download
Specifications
| SKU / Model | 3VA5110-4ED31-0AA0 |
|---|---|
| Brand | SIEMENS |
| product brand name | SENTRON |
| product designation | Molded-case circuit breaker |
| product designation / according to UL file | SEAS |
| Product version | System protection |
| design of the load switch / acc. to UL 489 / Heating, Air Conditioning, and Refrigeration circuit breaker (HACR Type) | Yes |
| design of the load switch / acc. to UL 489 / High-Intensity-Discharge circuit breaker (HID Type) | No |
| design of the load switch / acc. to UL 489 / Switching Duty circuit breaker (SWD Type) | No |
| design of the overcurrent release | TM210 |
| protection function of the overcurrent release | LI |
| number of poles | 3 |
| rated insulation voltage Ui | 800 V |
| Max. rated operational voltage Ue with DC | 500 V |
| power loss [W] / maximum | 22.8 W |
| Active power loss / for rated value of the current / at AC / in hot operating state / per pole | 7.6 W |
| mechanical service life (switching cycles) / typical | 20 000 |
| Electrical endurance (switching cycles) / at AC-1 / at 380/415 V 50/60 Hz | 8 000 |
| Electrical endurance (switching cycles) / at AC-1 / at 690 V 50/60 Hz | 4 000 |
| electrical endurance (switching cycles) / at 480 V | 8 000 |
| electrical endurance (switching cycles) / at 600 V | 4 000 |
| Neutral conductors / upgradeable/retrofittable | No |
| product function | - |
| ● communication function | No |
| ● other measurement function | No |
| marking / acc. to UL 489 / 100%-rated breaker | No |
| operational current | - |
| ● at 40 °C | 100 A |
| ● at 45 °C | 98 A |
| ● at 50 °C | 95 A |
| ● at 55 °C | 93 A |
| ● at 60 °C | 91 A |
| ● at 65 °C | 89 A |
| ● at 70 °C | 87 A |
| switching capacity class of the circuit breaker | S |
| breaking capacity maximum short-circuit current (Icu) | - |
| breaking capacity operating short-circuit current (Ics) | - |
| short-circuit current making capacity (Icm) | - |
| ● at 415 V | 75.6 kA |
| ● at 690 V | 7.5 kA |
| design of short-circuit protection | For switching power values in DC networks, see the 3VA molded case circuit breaker device manual; link to be found under Service & Support in the last chapter |
| breaking capacity current | - |
| ● at 240 V | 65 kA |
| ● at 480 V | 25 kA |
| ● at 600 Y/347 V | 14 kA |
| Adjustable response value current / lg min. | 100 A |
| Ground fault protection / tripping switchable / I2t=ON/OFF | No |
| height [in] | 5.51 in |
| Height | 140 mm |
| width [in] | 3 in |
| Width | 76.2 mm |
| depth [in] | 3.01 in |
| arrangement of electrical connectors / for main current circuit | Without connection |
| type of electrical connection / for main current circuit | Without |
| product component | - |
| ● undervoltage release | No |
| ● voltage trigger | No |
| ● trip indicator | No |
| number of CO contacts / for auxiliary contacts | 0 |
| product extension / optional / motor drive | Yes |
| protection class IP / on the front | IP40 |
| ambient temperature | - |
| ● during operation / minimum | -25 °C |
| ● during operation / maximum | 70 °C |
| ● during storage / minimum | -40 °C |
| ● during storage / maximum | 80 °C |
| reference code / acc. to IEC 81346-2 | Q |
| certificate of suitability / as approval for NAVAL (no combat vessels) / supplement SB | No |
| last modified: | 10/11/2021 |
| Weight | 0.990 kg |
| Dimensions | 35125254803-210.100100 × -10 mm |
Need bulk pricing or a hard-to-find part?
Request a quote for project quantities, discontinued or obsolete models, and pro-forma invoice / bank transfer orders. Our sourcing team responds fast.