[ez-toc]
Overview
- Can only be plugged onto ET 200M with IM 153-2 and IM 153-2 FO
- 8 AO HART
- Redundant connection
- Firmware update
- HART secondary variables
Note:
SIPLUS extreme products are based on SIMATIC standard products. The contents listed here were taken from the respective standard products. SIPLUS extreme-specific information was added.
For technical documentation on SIPLUS, see:
http://www.siemens.com/siplus-extreme
Design
- 8 analog channels per module
- Selectable output range per channel:
- 0 to 20 mA (with/without HART function);
- 4 to 20 mA (with/without HART function)
Function
- 8 outputs (current)
- Type of output can be selected for each channel
- Channel-by-channel configuration using parameter data record 1 or HART data records 131-138
- Configurable diagnosis (per channel) and diagnostic alarm (for entire assembly)
- Analog outputs can be read back
- The assembly can be dynamically reconfigured channel by channel in RUN (CiR-capable)
- Configuration of HART ancillary variables 1)
- Redundant operation1)
- Discrepancy analysis when used in automation system S7-400H
1) Possible from IM153-2 (6ES7 153-2BAx2-0XB0) onwards
6AG1332-8TF01-2AB0
Siemens SIPLUS S7-300 SM 332 8AQ HART based on 6ES7332-8TF01-0AB0 with conformal coating, -25…+60 °C, analog output 8 AQ 0/4 – 20 mA HART, for ET 200M with IM 153-2, IM 153-2, 20-pole functions: firmware update, HART auxiliary variables, redundancy, local diagnostic buffer with time stamping, requirement: PCS 7 V7.0, SP1